Water Purification Plants

Summary

<p>In Pune city, there are 16 water treatment plants operated by the Municipal Corporation. The details and treatment capacities are as follows:</p>
<div class="table-responsive">
<table class="text-start">
<thead>
<tr>
<th>Sr. No.</th>
<th>Water Treatment Plant</th>
<th>Capacity (MLD)</th>
<th>Operating Period (in Years)</th>
</tr>
</thead>
<tbody>
<tr>
<td>1.</td>
<td>Parvati (New)</td>
<td class="text-center">500</td>
<td class="text-center">6</td>
</tr>
<tr>
<td>2.</td>
<td>Parvati (Old)</td>
<td class="text-center">350</td>
<td class="text-center">55</td>
</tr>
<tr>
<td>3.</td>
<td>Lashkar (New)</td>
<td class="text-center">125</td>
<td class="text-center">18</td>
</tr>
<tr>
<td>4.</td>
<td>Lashkar (Old)</td>
<td class="text-center">300</td>
<td class="text-center">130</td>
</tr>
<tr>
<td>5.</td>
<td>Chikhali</td>
<td class="text-center">29</td>
<td class="text-center">25</td>
</tr>
<tr>
<td>6.</td>
<td>Holkar (New)</td>
<td class="text-center">45</td>
<td class="text-center">18</td>
</tr>
<tr>
<td>7.</td>
<td>Holkar (Old)</td>
<td class="text-center">10</td>
<td class="text-center">130</td>
</tr>
<tr>
<td>8.</td>
<td>Warje (New)</td>
<td class="text-center">200</td>
<td class="text-center">10</td>
</tr>
<tr>
<td>9.</td>
<td>Warje (Old)</td>
<td class="text-center">180</td>
<td class="text-center">18</td>
</tr>
<tr>
<td>10.</td>
<td>Wadgaon (New)</td>
<td class="text-center">125</td>
<td class="text-center">10</td>
</tr>
<tr>
<td>11.</td>
<td>Wadgaon (Old)</td>
<td class="text-center">125</td>
<td class="text-center">18</td>
</tr>
<tr>
<td>12.</td>
<td>Bhama Askhed (Kuruli)</td>
<td class="text-center">200</td>
<td class="text-center">3</td>
</tr>
<tr>
<td>13.</td>
<td>Kondhwe Dhavde (Newly Included Village)</td>
<td class="text-center">10</td>
<td class="text-center">10</td>
</tr>
<tr>
<td>14.</td>
<td>Wagholi</td>
<td class="text-center">5</td>
<td class="text-center">10</td>
</tr>
<tr>
<td>15.</td>
<td>Fursungi, Uruli</td>
<td class="text-center">5</td>
<td class="text-center">33</td>
</tr>
<tr>
<td>16.</td>
<td>Vadu</td>
<td class="text-center">5</td>
<td class="text-center">2</td>
</tr>
</tbody>
</table>
</div>

<p>&nbsp;</p><p>In addition, the 33 MLD water treatment project at Fursungi, as well as the 12 MLD project at Manjari, are in the final stages under Maharashtra Jeevan Pradhikaran. Once completed, these projects will be transferred to the Pune Municipal Corporation.</p><h3><strong>Regarding the Quality of Drinking Water</strong></h3><ul><li>Drinking water is supplied to Pune city through 14 water centers located at 11 sites managed by the Pune Municipal Corporation Water Supply Department.</li><li>The Water Supply Department maintains a central testing laboratory at the Parvati Water Center where physical, chemical, and biological analyses are conducted.</li><li>Approximately 15,000 water samples are collected every month from all water centers, distribution reservoirs, and various taps in the city for testing.</li><li>Daily tests are conducted on 40 parameters of drinking water as prescribed by the Indian Standard ‘IS10500:2012’.</li><li>Continuous testing is carried out at various stages in the water treatment centers to ensure the effectiveness of the purification process.</li><li>A consolidated report of the water sample tests is submitted every month to the Maharashtra State Health Laboratory, Pune.</li><li>Since April 2022, the water testing reports have been made available in the public domain on the website

<h3 class="mt-3">Water Sample Testing</h3>
<div class="row mb-3">
<div class="col-md-6"><a href="https://drive.google.com/drive/folders/1Xt5INZ3O6KATHmZm65-3sriwoV0kVjV…; class="card-link-clickble border-lightGray text-darkGray text-decoration-none rounded-24 d-flex align-items-center font-20 inter fw-normal position-relative" target="_blank">Inspection report of the source</a></div>
</div>
</li><li>The detailed water testing parameters maintained by the department’s laboratory are available for public reference.</li><li>The list of testing parameters along with the specifications as per IS10500:2012 is provided below.</li></ul><p>&nbsp;</p>

<div class="table-responsive">
<table class="text-start">
<thead>
<tr>
<th>Sr. No.</th>
<th>Parameters</th>
<th>Desirable</th>
<th>Permissible</th>
<th>Unit</th>
</tr>
</thead>
<tbody>
<!-- Section A: Physical Parameters -->
<tr style="background-color: #f1f1f1; font-weight: bold;">
<td colspan="5">A) PHYSICAL PARAMETERS</td>
</tr>
<tr>
<td>1</td>
<td>Colour</td>
<td>Max. 5.0</td>
<td>Max. 15</td>
<td>Hazen</td>
</tr>
<tr>
<td>2</td>
<td>Turbidity</td>
<td>Max. 1</td>
<td>Max. 5</td>
<td>N.T.U.</td>
</tr>
<tr>
<td>3</td>
<td>Odour</td>
<td>--</td>
<td>--</td>
<td>--</td>
</tr>
<tr>
<td>4</td>
<td>Taste</td>
<td>--</td>
<td>--</td>
<td>--</td>
</tr>
<!-- Section B: Chemical Parameters -->
<tr style="background-color: #f1f1f1; font-weight: bold;">
<td colspan="5">B) CHEMICAL PARAMETERS</td>
</tr>
<tr>
<td>5</td>
<td>pH</td>
<td>Between 6.5 to 8.5 </td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>6</td>
<td>Total Hardness (as CaCo<sub>3</sub>)</td>
<td>Max 200</td>
<td>Max 600</td>
<td>PPM</td>
</tr>
<tr>
<td>7</td>
<td>Ca Hardness</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>8</td>
<td>Mg Hardness</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>9</td>
<td>Ca<sup>++</sup></td>
<td>Max 75</td>
<td>Max 200</td>
<td>PPM</td>
</tr>
<tr>
<td>10</td>
<td>Mg<sup>++</sup></td>
<td>Max 30</td>
<td>Max 100</td>
<td>PPM</td>
</tr>
<tr>
<td>11</td>
<td>Alkalinity</td>
<td>Max 200</td>
<td>Max 600</td>
<td>PPM</td>
</tr>
<tr>
<td>12</td>
<td>Chlorides</td>
<td>Max 250</td>
<td>Max 1000</td>
<td>PPM</td>
</tr>
<tr>
<td>13</td>
<td>Nitrate Nitrogen</td>
<td>Max 45</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>14</td>
<td>Nitrite Nitrogen</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>15</td>
<td>Iron</td>
<td>Max 0.3</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>16</td>
<td>Fluorides</td>
<td>Max 1.0</td>
<td>Max 1.5</td>
<td>PPM</td>
</tr>
<tr>
<td>17</td>
<td>Aluminium</td>
<td>Max 0.03</td>
<td>Max 0.2</td>
<td>PPM</td>
</tr>
<tr>
<td>18</td>
<td>Sulphide</td>
<td>Max 0.05</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>19</td>
<td>Phosphate</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>20</td>
<td>Ammonia (mg/l)</td>
<td>Max 0.5</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>21</td>
<td>Surfactant</td>
<td>Max 0.2</td>
<td>Max 1.0</td>
<td>PPM</td>
</tr>
<tr>
<td>22</td>
<td>Chloramine</td>
<td>Max 4.0</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>23</td>
<td>Potassium</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>24</td>
<td>Copper</td>
<td>Max 0.5</td>
<td>Max 1.5</td>
<td>PPM</td>
</tr>
<tr>
<td>25</td>
<td>Manganese</td>
<td>Max 0.1</td>
<td>Max 0.3</td>
<td>PPM</td>
</tr>
<tr>
<td>26</td>
<td>Phenolic Compound</td>
<td>Max 0.001</td>
<td>Max 0.002</td>
<td>PPM</td>
</tr>
<tr>
<td>27</td>
<td>Molybdenum</td>
<td>Max 0.07</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>28</td>
<td>Cyanide</td>
<td>Max 0.05</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>29</td>
<td>Conductivity</td>
<td>--</td>
<td>--</td>
<td>ms</td>
</tr>
<tr>
<td>30</td>
<td>TDS</td>
<td>Max 500</td>
<td>Max 2000</td>
<td>PPM</td>
</tr>
<tr>
<td>31</td>
<td>D.O.</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>32</td>
<td>Temperature</td>
<td>--</td>
<td>--</td>
<td>°C</td>
</tr>
<tr>
<td>33</td>
<td>Sodium</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>34</td>
<td>Lithium</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>35</td>
<td>Lead</td>
<td>Max 0.01</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>36</td>
<td>Cadmium</td>
<td>Max 0.003</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>37</td>
<td>Zinc</td>
<td>Max 5</td>
<td>Max 15</td>
<td>PPM</td>
</tr>
<tr>
<td>38</td>
<td>Sulphate</td>
<td>Max 200</td>
<td>Max 400</td>
<td>PPM</td>
</tr>
<tr>
<td>39</td>
<td>Boron</td>
<td>Max 0.5</td>
<td>Max 1.0</td>
<td>PPM</td>
</tr>
<tr>
<td>40</td>
<td>Nickel</td>
<td>Max 0.02</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>41</td>
<td>TOC</td>
<td>--</td>
<td>--</td>
<td>PPM</td>
</tr>
<tr>
<td>42</td>
<td>Arsenic</td>
<td>Max 0.01</td>
<td>Max 0.05</td>
<td>PPM</td>
</tr>
<tr>
<td>43</td>
<td>Silver</td>
<td>Max 0.1</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>44</td>
<td>Mercury</td>
<td>Max 0.001</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>45</td>
<td>Chromium</td>
<td>Max 0.05</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>46</td>
<td>Selenium</td>
<td>Max 0.01</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>47</td>
<td>Barium</td>
<td>Max 0.7</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<tr>
<td>48</td>
<td>Mineral Oil</td>
<td>Max 0.5</td>
<td>No Relaxation</td>
<td>PPM</td>
</tr>
<!-- Section C: Bacteriological Testing -->
<tr style="background-color: #f1f1f1; font-weight: bold;">
<td colspan="5">C) Bacteriological Testing</td>
</tr>
<tr>
<td>49</td>
<td>Coliform</td>
<td>0</td>
<td>0</td>
<td>100 ml</td>
</tr>
<tr>
<td>50</td>
<td>E-Coliform</td>
<td>0</td>
<td>0</td>
<td>100 ml</td>
</tr>
<tr>
<td>51</td>
<td>Residual Chlorine Test</td>
<td>Min 0.2</td>
<td>Min 1</td>
<td>PPM</td>
</tr>
</tbody>
</table>
</div>

<h3><strong>Precautions for Maintaining Quality that Citizens Should Take</strong></h3>
<ol>
<li>Drinking water should always be stored in a clean environment and in clean containers.</li>
<li>If the drinking water supplied by the Municipal Corporation is stored in a society’s basement or other storage tanks, ensure that the surrounding area is kept clean. All water tanks in the society should be cleaned at regular intervals.</li>
<li>Take care to ensure that no water from external sources, which may not be properly treated or verified, is mixed into the drinking water tank supplied by the Municipal Corporation.</li>
<li>Ensure that no sewage or similar water is stored near the drinking water tank or allowed to flow directly into it.</li>
<li>When undertaking any plumbing work at home, verify that the pipelines for drinking water and other water supplies remain separate and do not get mixed.</li>
<li>For the convenience of citizens, a paid water testing facility has been made available at the Parvati Water Center Laboratory, located opposite Bhandari Hotel, Sinhagad Road, Ganeshmala, Pune-30. The challan (payment receipt) for water testing can be issued between 9:00 AM and 12:30 PM, excluding Saturdays, Sundays, and all government holidays. The water testing report will be provided on the fifth working day after submitting the water sample. To collect the test report, a photocopy of the paid challan must be submitted at the laboratory.</li>
</ol>
<div class="table-responsive">
<table>
<thead>
<tr>
<th>Sr. No</th>
<th>Parameter</th>
<th>Rate</th>
</tr>
</thead>
<tbody>
<tr>
<td>1</td>
<td>TURBIDITY</td>
<td>140</td>
</tr>
<tr>
<td>2</td>
<td>Ph</td>
<td>50</td>
</tr>
<tr>
<td>3</td>
<td>HARDNESS</td>
<td>190</td>
</tr>
<tr>
<td>4</td>
<td>ALKALINITY</td>
<td>190</td>
</tr>
<tr>
<td>5</td>
<td>CHLORIDES</td>
<td>190</td>
</tr>
<tr>
<td>6</td>
<td>NITRATE</td>
<td>190</td>
</tr>
<tr>
<td>7</td>
<td>NITRITE</td>
<td>190</td>
</tr>
<tr>
<td>8</td>
<td>MPN</td>
<td>340</td>
</tr>
<tr>
<td>9</td>
<td>TDS</td>
<td>190</td>
</tr>
<tr>
<td>10</td>
<td>IRON</td>
<td>240</td>
</tr>
<tr>
<td>11</td>
<td>FLUORIDES</td>
<td>240</td>
</tr>
<tr>
<td>12</td>
<td>CALCIUM</td>
<td>200</td>
</tr>
<tr>
<td>13</td>
<td>MAGNESIUM</td>
<td>190</td>
</tr>
<tr>
<td>14</td>
<td>ALUMINIUM</td>
<td>410</td>
</tr>
<tr>
<td>15</td>
<td>SULPHIDE</td>
<td>200</td>
</tr>
<tr>
<td>16</td>
<td>PHOSPHATE</td>
<td>190</td>
</tr>
<tr>
<td>17</td>
<td>POTASSIUM</td>
<td>190</td>
</tr>
<tr>
<td>18</td>
<td>CYANIDE</td>
<td>370</td>
</tr>
<tr>
<td>19</td>
<td>CONDUCTIVITY</td>
<td>140</td>
</tr>
<tr>
<td>20</td>
<td>D.O</td>
<td>190</td>
</tr>
<tr>
<td>21</td>
<td>SODIUM</td>
<td>190</td>
</tr>
<tr>
<td>22</td>
<td>LITHIUM</td>
<td>410</td>
</tr>
<tr>
<td>23</td>
<td>ZINC</td>
<td>240</td>
</tr>
<tr>
<td>24</td>
<td>CADMIUM</td>
<td>340</td>
</tr>
<tr>
<td>25</td>
<td>LEAD</td>
<td>340</td>
</tr>
<tr>
<td>26</td>
<td>BORON</td>
<td>410</td>
</tr>
<tr>
<td>27</td>
<td>SULPHATE</td>
<td>190</td>
</tr>
<tr>
<td>28</td>
<td>MOLYBDENUM</td>
<td>410</td>
</tr>
<tr>
<td>29</td>
<td>NICKEL</td>
<td>410</td>
</tr>
<tr>
<td>30</td>
<td>TOC</td>
<td>370</td>
</tr>
<tr>
<td>31</td>
<td>TSS</td>
<td>240</td>
</tr>
<tr>
<td>32</td>
<td>ACIDITY</td>
<td>140</td>
</tr>
<tr>
<td>33</td>
<td>SILICA</td>
<td>190</td>
</tr>
<tr>
<td>34</td>
<td>BOD</td>
<td>370</td>
</tr>
<tr>
<td>35</td>
<td>AMMONIA</td>
<td>240</td>
</tr>
<tr>
<td>36</td>
<td>COD</td>
<td>370</td>
</tr>
<tr>
<td>37</td>
<td>OIL & GREASE</td>
<td>370</td>
</tr>
<tr>
<td>38</td>
<td>ARSENIC</td>
<td>240</td>
</tr>
<tr>
<td>39</td>
<td>MANGANESE</td>
<td>240</td>
</tr>
<tr>
<td>40</td>
<td>COBALT</td>
<td>410</td>
</tr>
<tr>
<td>41</td>
<td>CHROMIUM</td>
<td>340</td>
</tr>
<tr>
<td>42</td>
<td>COPPER</td>
<td>340</td>
</tr>
<tr>
<td>43</td>
<td>MERCURY</td>
<td>340</td>
</tr>
<tr>
<td>44</td>
<td>SELENIUM</td>
<td>410</td>
</tr>
<tr>
<td>45</td>
<td>SILVER</td>
<td>340</td>
</tr>
<tr>
<td>46</td>
<td>RESIDUAL CHLORINE</td>
<td>140</td>
</tr>
<tr>
<td colspan="2" align="right"><strong>TOTAL</strong></td>
<td><strong>12260</strong></td>
</tr>
</tbody>
</table>
</div>